SCM50ZS-S1

Nominal cooling capacity: 5.0(1.8~7.1) - Multi Outdoor Unit RAC

SCM50ZS-S1

Multi Outdoor Unit RAC

Nominal cooling capacity of 5.0kW

Power source1Phase, 220 - 240V, 50Hz
Nominal cooling capacity (Min~Max)kW5.0(1.8~7.1)
Nominal heating capacity (Min~Max)kW6.0(1.4~7.5)
Power consumptionCooling/HeatingkW1.05(0.60~2.15) / 1.21(0.55~2.58)
EER/COPCooling/Heating4.76 / 4.96
Max. running currentA14
Sound power
level
CoolingdB(A)61
Heating63
Sound pressure
level
CoolingdB(A)48
Heating50
Air flowCoolingm3/min41.0
Heating41.0
Exterior DimensionsHeight x Width x Depthmm640 ×850(+65) ×290
Net weightkg49.0
RefrigerantType/GWPR410A/2088
Chargekg/TCO2Eq2.5/5.22
Refrigerant piping sizeLiquid/Gasø mm6.35(1/4") ×3 / 9.52(3/8") ×3
Outdoor operating
temperature range
Cooling°C-15~43
Heating-15~24
Number of Connectable indoor unitsMin.2~Max.3
Total indoor units capacity8.5
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
• In case of SRK71ZR + SRK71ZR, 2 Indoor units can be connectable. The total connecting capacity of indoor units should be between 100 ~ 160.