SAF350E7

VRF Indoor Unit

SAF350E7

Fresh Air Ventilation and Heat Exchange VRF Indoor Unit

Nominal cooling capacity of 350m3/hr

Power Source 1 Phase 220-240V, 50Hz
Exterior dimensions Height x Width x Depth mm 317x1050x804
Exterior appearance Galvanized steel sheet
Power input W 178-185
Running current A 0.81-0.77
Capacity UHi Enthalpy exchange efficiency Cooling % 66
Heating 69
Temperature exchange efficiency 75
Capacity Hi Enthalpy exchange efficiency Cooling 66
Heating 69
Temperature exchange efficiency 75
Capacity Lo Enthalpy exchange efficiency Cooling 71
Heating 73
Temperature exchange efficiency 78
Motor & Q'ty W 40 x 2
Air handling equipment Fan type & Q’ty Sirocco fan x 2
Air flow UHi m3/h 350
Hi 350
Lo 240
External static pressure UHi Pa 140
Hi 60
Lo 45
Net weight kg 49
Remote Control Included
Air filter Supply air Protection for element (Washable) PS400
Exhaust air
The data are measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19oCWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
External static pressure of indoor unit is 10Pa.
The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.