| Nominal cooling capacity | kW | 9.0 | ||
| Nominal heating capacity | kW | 10.0 | ||
| Power source | 1 Phase 220-240V, 50Hz | |||
| Power consumption | Cooling | kW | 240-250 | |
| Heating | kW | 240-250 | ||
| Sound power level | Cooling | dB(A) | 63 | |
| Heating | 65 | |||
| Sound pressure level Cooling | db(A) | P-Hi:37 Hi:31 Me:27 Lo:22 | ||
| Sound pressure level Heating | db(A) | P-Hi:39 Hi:33 Me:28 Lo:23 | ||
| Exterior dimensions unit | H x W x D | mm | 280x950x635 | |
| Net weight | kg | 34 | ||
| Air flow cooling | m3/min | P-Hi:24 Hi:19 Me:15 Lo:10 | ||
| Air flow heating | m3/min | P-Hi:24 Hi:19 Me:15 Lo:10 | ||
| Maximum external static pressure | Pa | 200 | ||
| Outside air intake | Possible | |||
| Refrigerant piping size (liquid/ gas) | mm (⌀ inch) | Liquid line:ø9.52(3/8")(Flare) Gas line:ø15.88(5/8")(Flare) | ||
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.