FDU650FKXZE1

VRF Indoor Unit

FDU650FKXZE1

Air Processing VRF Indoor Unit

Nominal cooling capacity of 11m3/min

Nominal cooling capacity kW 9.0
Nominal heating capacity kW 6.5
Power source 1 Phase 220-240V, 50Hz
Power consumption Cooling kW 0.24-0.25
Heating kW 0.24-0.25
Sound pressure level Cooling db(A) Hi:31
Exterior dimensions unit H x W x D mm 280x950x635
Net weight kg 34
Air flow m3/min Hi:11
Maximum external static pressure Pa 200 (at Hi Air flow)
Air filter, Q'ty Procure locally
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Refrigerant piping size mm(in) Liquid line:ø9.52(3/8") Gas line:ø15.88(5/8")
The data are measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19oCWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
External static pressure of indoor unit is 10Pa.
The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.