FDU2400FKXZE1

VRF Indoor Unit

FDU2400FKXZE1

Air Processing VRF Indoor Unit

Nominal cooling capacity of 40m3/min

Nominal cooling capacitykW28.0
Nominal heating capacitykW21.5
Power source1 Phase 220-240V, 50Hz
Power consumptionCoolingkW1.16-1.20
HeatingkW1.16-1.20
Sound pressure level Coolingdb(A)Hi:45
Exterior dimensions unitH x W x Dmm379x1600x893
Net weightkg89
Air flow coolingm3/minHi:40
Maximum external static pressurePa200 (at Hi Air flow)
Remote control (option)wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Refrigerant piping size (liquid/ gas)mm(in)Liquid line:ø9.52(3/8") Gas line:ø22.22(7/8")
The data are measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19oCWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
External static pressure of indoor unit is 10Pa.
The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.