FDK90KXZE1

VRF Indoor Unit

FDK90KXZE1

Wall Mounted VRF Indoor Unit

Nominal cooling capacity of 9.0kW

Nominal cooling capacity kW 9.0
Nominal heating capacity kW 10.0
Power source 1 Phase 220-240V, 50Hz
Power consumption Cooling kW 0.05-0.05
Heating kW 0.05-0.05
Sound power level dB(A) 61
Sound pressure level Cooling db(A) P-Hi:44 Hi:42 Me:39 Lo:35
Sound pressure level Heating db(A) P-Hi:44 Hi:42 Me:39 Lo:35
Exterior dimensions unit H x W x D mm 339 x 1197 x 262
Net weight kg 17
Air flow m3/min P-Hi:23 Hi:21 Me:19 Lo:16
Outside air intake Not possible
Air filter, Q'ty Polypropylene net x2 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-K-E2, RCN-K71-E2
Installation data Refrigerant piping size mm(in) Liquid line:ø9.52(3/8") Gas line:ø15.88(5/8")
The data are measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19oCWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
External static pressure of indoor unit is 10Pa.
The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.