| Nominal cooling capacity | kW | 5.6 | ||
| Nominal heating capacity | kW | 6.3 | ||
| Power source | 1 Phase 220-240V 50Hz / 220v 60Hz | |||
| Power consumption | Cooling | kW | 0.27-0.25 / 0.27 | |
| Heating | kW | 0.27-0.25 / 0.27 | ||
| Sound power level | Cooling | dB(A) | 58 | |
| Heating | 61 | |||
| Sound pressure level Cooling | db(A) | P-Hi:43 Hi:41 Me:36 Lo:33 | ||
| Sound pressure level Heating | db(A) | P-Hi:43 Hi:41 Me:36 Lo:33 | ||
| Exterior dimensions unit | H x W x D | mm | 290 x 870 x 230 | |
| Net weight | kg | 11.5 | ||
| Air flow cooling | m3/min | P-Hi:12 Hi:11 Me:9 Lo:8 | ||
| Air flow heating | m3/min | P-Hi:13 Hi:12 Me:10 Lo:8 | ||
| Outside air intake | Not possible | |||
| Air filter, Q'ty | Polypropylene net x2 (Washable) | |||
| Remote control (option) | wired:RC-EX3D, RC-E5, RCH-E3 wireless:RCN-K-E2 | |||
| Refrigerant piping size (liquid/ gas) | mm (⌀ inch) | Liquid line : ø6.35 (1/4") Gas line : ø12.7 (1/2") | ||
| Refrigerant | Type/GWP | R32 | ||
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.