FDE50VH

Multi Indoor Unit RAC

FDE50VH

Ceiling Suspended Multi Indoor Unit RAC

Nominal cooling capacity of 5.0kW

Nominal cooling capacitykW5.0
Nominal heating capacitykW5.8
Sound power levelCoolingdB(A)60
HeatingdB(A)60
Sound pressure levelCooling(Hi/Me/Lo/Ulo)dB(A)46 / 38/ 36/ 31
Heating(Hi/Me/Lo/Ulo)dB(A)46 / 38/ 36/ 31
Air flowCooling(Hi/Me/Lo/Ulo)m3/min13.0 / 10.0 / 9.0 / 7.0
Heating(Hi/Me/Lo/Ulo)m3/min13.0 / 10.0 / 9.0 / 7.0
Exterior dimensions (H×W×D)mm210×1070×690
Net weightkg28.0
Refrigerant piping sizeLiquid / Gasmm ⌀6.35(1/4") / 12.7(1/2")
Clean filterPocket Plastic net × 2 (Washable)
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.