FDE36KXZE1

VRF Indoor Unit

FDE36KXZE1

Ceiling Suspended VRF Indoor Unit

Nominal cooling capacity of 3.6kW

Nominal cooling capacity kW 3.6
Nominal heating capacity kW 4.0
Power source 1 Phase 220-240V, 50Hz
Power consumption Cooling kW 0.05-0.05
Heating kW 0.05-0.05
Sound power level dB(A) 60
Sound pressure level Cooling db(A) P-Hi:46 Hi:38 Me:31 Lo:26
Exterior dimensions unit H x W x D mm 210 x 1070 x 690
Net weight kg 28
Air flow m3/min P-Hi:13 Hi:10 Me:7 Lo:5.5
Outside air intake Not possible
Air filter, Q'ty Pocket Plastic net x2 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-E-E3
Installation data Refrigerant piping size mm(in) Liquid line:ø6.35(1/4") Gas line:ø12.7(1/2")
The data are measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19oCWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
External static pressure of indoor unit is 10Pa.
The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.