FDCH560KXE6

VRF Outdoor Unit

FDCH560KXE6

High Head Series Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 56.0kW
R410A

Nominal horse power 20HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 8
Max Current A 47
Nominal capacity Cooling kW 56.0
Heating 63.0
Electrical characteristics
Power Consumption
Cooling kW 16.79
Heating 16.79
Exterior dimensions HxWxD mm 2048x1350x720
Sound pressure level Cooling/Heating dB(A) 63.0 / 63.0
Net Weight kg 358
Refrigerant Type / GWP R410A / 2088
Refrigerant Charge kg/TCO2Eq 11.5 / 24.012
Refrigerant piping size Liquid line mm(in) ø15.88(5/8")
Refrigerant piping size Gas line mm(in) ø28.58(1 1/8")
Capacity connection % 50~140
Number of connectable indoor units 40
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.