FDCH1235KXE6

VRF Outdoor Unit

FDCH1235KXE6

High Head Series Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 123.5kW

Combination (FDC) 615KXE6 + 615KXE6
Nominal horse power 44HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 16
Max Current A 94
Nominal capacity Cooling kW 123.5
Heating 138.0
Electrical characteristics
Power Consumption
Cooling kW 40.74
Heating 36.96
Exterior dimensions HxWxD mm 2048x2700x720
Net Weight kg 377x2
Refrigerant charge R410A kg 11.5x2
Refrigerant piping size Liquid line mm(in) ø22.22(7/8")
Refrigerant piping size Gas line mm(in) ø38.1(1 1/2")
Capacity connection % 50~130
Number of connectable indoor units 72
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.