FDC850KXZXE1

VRF Outdoor Unit

FDC850KXZXE1

Hi COP Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 85.0kW

Combination (FDC)280KXZXE1 + 280KXZXE1 + 280KXZXE1
Nominal horse power30HP
Power source3 Phase 380-415V, 50Hz
Starting currentA15
Max CurrentA96
Nominal capacityCoolingkW85.0
Heating95.0
Electrical characteristics
Power Consumption
CoolingkW21.1
Heating20.6
Exterior dimensionsHxWxDmm2048x4050x720
Net Weightkg975
Refrigerant chargeR410Akg11.5x3
Refrigerant piping sizeLiquid linemm(in)ø15.88(5/8")
Refrigerant piping sizeGas linemm(in)ø31.75(1 1/4")[ø34.92(1 3/8")]
Refrigerant piping sizeOil equalizationmm(in)ø9.52(3/8")
Capacity connection%160
Number of connectable indoor units80
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.