FDC850KXZE1

VRF Outdoor Unit

FDC850KXZE1

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 85.0kW

Combination (FDC) 400KXZE1 + 450KXZE1
Nominal horse power 30HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 10
Max Current A 64
Nominal capacity Cooling kW 85.0
Heating 95.0
Electrical characteristics
Power Consumption
Cooling kW 24.94
Heating 23.19
Exterior dimensions HxWxD mm 2048x2700x720
Net Weight kg 634
Refrigerant charge R410A kg 11.5x2
Refrigerant piping size Liquid line mm(in) ø15.88(5/8")
Refrigerant piping size Gas line mm(in) ø31.75(1 1/4") [ø34.92(1 3/8")]
Capacity connection % 50~130
Number of connectable indoor units 73
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.