| Combination (FDC) | FDC400KXZE3 / FDC400KXZE3 | |||
| Nominal horse power | 28HP | |||
| Power source | 3 Phase 380-415V 50Hz / 380V 60Hz | |||
| Max Current | A | 64.8 | ||
| Nominal capacity | Cooling | kW | 80 | |
| Heating | 80 | |||
| Electrical characteristics Power Consumption | Cooling | kW | 23.5 | |
| Heating | 17.7 | |||
| EER | Cooling | 3.41 | ||
| COP | Heating | 4.75 | ||
| Net Weight | kg | 704 | ||
| Refrigerant | Type / GWP | R32 / 675 | ||
| Refrigerant charge | R32 | kg | 8.7 + 8.7 | |
| Refrigerant piping size | Liquid line | mm (⌀ inch) | ø15.88 (5/8") | |
| Refrigerant piping size | Gas line | mm (⌀ inch) | ø34.92 (1.3/8") | |
| Refrigerant piping size | Oil equalization | mm (⌀ inch) | ø12.7 (1/2") | |
| Capacity connection | % | 50~150 | ||
| Number of connectable indoor units | 80 | |||
| SEER / SCOP (Outdoor unit) | 8.58 / 4.52 | |||
The data are measured under the following conditions (ISO-T1, H1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
SEER/SCOP are based on EN14825:2018 and Commission regulation (EU) No.2016/2281. Temperature conditions for calculating SCOP are based on "Average climate".
Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
Refrigerant contained in the products is a fluorinated greenhouse gas listed in Regulation (EU) No 517/2014.
When connecting the indoor unit type FDK, FDFL, FDFU or FDFW series, limit the connectable capacity not higher than 130%.
SEER/SCOP are based on EN14825:2018 and Commission regulation (EU) No.2016/2281. Temperature conditions for calculating SCOP are based on "Average climate".
Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
Refrigerant contained in the products is a fluorinated greenhouse gas listed in Regulation (EU) No 517/2014.
When connecting the indoor unit type FDK, FDFL, FDFU or FDFW series, limit the connectable capacity not higher than 130%.