FDC735KXZXE1

VRF Outdoor Unit

FDC735KXZXE1

Hi COP Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 73.5kW

Combination (FDC) 224KXZXE1 + 224KXZXE1 + 280KXZXE1
Nominal horse power 26HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 15
Max Current A 74.4
Nominal capacity Cooling kW 73.5
Heating 82.5
Electrical characteristics
Power Consumption
Cooling kW 17.1
Heating 18.2
Exterior dimensions HxWxD mm 2048x4050x720
Net Weight kg 885
Refrigerant charge R410A kg 11.0x2+11.5
Refrigerant piping size Liquid line mm(in) ø15.88(5/8")
Refrigerant piping size Gas line mm(in) ø31.75(1 1/4")[ø34.92(1 3/8")]
Refrigerant piping size Oil equalization mm(in) ø9.52(3/8")
Capacity connection % 160
Number of connectable indoor units 78
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.