FDC735KXZE1

VRF Outdoor Unit

FDC735KXZE1

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 73.5kW

Combination (FDC) 335KXZE1 + 400KXZE1
Nominal horse power 26HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 10
Max Current A 53.2
Nominal capacity Cooling kW 73.5
Heating 82.5
Electrical characteristics
Power Consumption
Cooling kW 19.92
Heating 19.73
Exterior dimensions HxWxD mm 2048x2700x720
Net Weight kg 589
Refrigerant charge R410A kg 11.0+11.5
Refrigerant piping size Liquid line mm(in) ø15.88(5/8")
Refrigerant piping size Gas line mm(in) ø31.75(1 1/4") [ø34.92(1 3/8")]
Capacity connection % 50~130
Number of connectable indoor units 63
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.