FDC500KXZE1

VRF Outdoor Unit

FDC500KXZE1

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 50.0kW
R410A

Nominal horse power 18HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 8
Max Current A 42.4
Nominal capacity Cooling kW 50.0
Heating 56.0
Electrical characteristics
Power Consumption
Cooling kW 13.97
Heating 13.49
Exterior dimensions HxWxD mm 2048x1350x720
Sound pressure level Cooling/Heating dB(A) 61/62
Net Weight kg 370
Refrigerant Type / GWP R410A / 2088
Refrigerant Charge kg/TCO2Eq 11.5 / 24.012
Refrigerant piping size Liquid line mm(in) ø12.7(1/2")
Refrigerant piping size Gas line mm(in) ø28.58(1 1/8")
Capacity connection % 50~130
Number of connectable indoor units 43
SEER / SCOP (Outdoor unit) 7.29 / 4.58
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.