FDC475KXZE1

VRF Outdoor Unit

FDC475KXZE1

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 47.5kW
R410A

Nominal horse power 17HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 8
Max Current A 42.4
Nominal capacity Cooling kW 47.5
Heating 53.0
Electrical characteristics
Power Consumption
Cooling kW 13.98
Heating 13.00
Exterior dimensions HxWxD mm 2048x1350x720
Sound pressure level Cooling/Heating dB(A) 61/61
Net Weight kg 370
Refrigerant Type / GWP R410A / 2088
Refrigerant Charge kg/TCO2Eq 11.5 / 24.012
Refrigerant piping size Liquid line mm(in) ø12.7(1/2")
Refrigerant piping size Gas line mm(in) ø28.58(1 1/8")
Capacity connection % 50~130
Number of connectable indoor units 41
SEER / SCOP (Outdoor unit) 6.84 / 4.31
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.