FDC280KXZE2

VRF Outdoor Unit

FDC280KXZE2

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of
R410A

Nominal horse power 10HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max Current A 20.1
Nominal capacity Cooling kW 28.0
Heating 31.5
Electrical characteristics
Power Consumption
Cooling kW 7.25
Heating 7.41
Exterior dimensions HxWxD mm 1697x1350x720
Sound pressure level Cooling/Heating dB(A) 56/57
Net Weight kg 288
Refrigerant Type / GWP R410A / 2088
Refrigerant Charge kg/TCO2Eq 11.0 / 22.968
Refrigerant piping size Liquid line mm(in) ø9.52(3/8")
Refrigerant piping size Gas line mm(in) ø22.22(7/8")
Capacity connection % 50~200
Number of connectable indoor units 37
The data are measured under the following conditions(ISO-T1,H1). Cooling: Indoor temp. of 27'CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20'CDB, and outdoor temp. of 7°CDB, 6°CWB.
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
'tonne(s) of CO, equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
[] : Pipe sizes applicable to European installations are shown in parentheses.