×

FDC224KXZME1

VRF Outdoor Unit

FDC224KXZME1

Micro Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 22.4kW R410A

Nominal horse power8HP
Power source3 Phase 380-415V, 50Hz
Starting currentA5
Max CurrentA20
Nominal capacityCoolingkW22.4
Heating22.4
Electrical characteristics
Power Consumption
CoolingkW5.59
Heating4.97
Exterior dimensionsHxWxDmm1675x1080x480
Sound pressure levelCooling/HeatingdB(A)58/59
Net Weightkg221
RefrigerantType / GWPR410A / 2088
RefrigerantChargekg/TCO2Eq11.5 / 24.012
Refrigerant piping sizeLiquid linemm(in)ø9.52(3/8")
Refrigerant piping sizeGas linemm(in)ø19.05(3/4")
Capacity connection%50~150
Number of connectable indoor units22
SEER / SCOP (Outdoor unit)6.55 / 4.55
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.