×

FDC224KXZE3

VRF Outdoor Unit

FDC224KXZE3

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 22.4kW R32

Nominal horse power8HP
Power source3 Phase 380-415V 50Hz / 380V 60Hz
Starting currentA5
Max CurrentA20.7
Nominal capacityCoolingkW22.4
Heating22.4
Electrical characteristics
Power Consumption
CoolingkW5.52
Heating4.58
EERCooling4.06
COPHeating4.90
Exterior dimensionsHxWxDmm1750×920×760
Sound pressure levelCooling/HeatingdB(A)55 / 55
Net Weightkg262
RefrigerantType / GWPR32 / 675
Refrigerant chargeR410Akg7.1
Refrigerant piping sizeLiquid linemm(in)ø9.52 (3/8”)
Refrigerant piping sizeGas linemm(in)ø19.05 (3/4")
Capacity connection%50~150
Number of connectable indoor units22
SEER / SCOP (Outdoor unit)9.16 / 4.82
The data are measured under the following conditions (ISO-T1, H1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
SEER/SCOP are based on EN14825:2018 and Commission regulation (EU) No.2016/2281. Temperature conditions for calculating SCOP are based on "Average climate".
Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
Refrigerant contained in the products is a fluorinated greenhouse gas listed in Regulation (EU) No 517/2014.
When connecting the indoor unit type FDK, FDFL, FDFU or FDFW series, limit the connectable capacity not higher than 130%.

We are currently experiencing technical issues with our Smart M Air App

For those of you who are still experiencing technical issues with our Smart M Air App, please update the app to the latest version via Google play (for Android) or Apple store (for iOS).