FDC2010KXZE3

VRF Outdoor Unit

FDC2010KXZE3

Standard Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 201.0kW R32

Combination (FDC)FDC670KXZE3 / FDC670KXZE3/ FDC670KXZE3
Nominal horse power72HP
Power source3 Phase 380-415V 50Hz / 380V 60Hz
Max CurrentA166.2
Nominal capacityCoolingkW201
Heating195
Electrical characteristics
Power Consumption
CoolingkW73.4
Heating47.3
EERCooling2.74
COPHeating4.12
Net Weightkg1335
RefrigerantType / GWPR32 / 675
Refrigerant charge R32kg9.5 + 9.5 + 9.5
Refrigerant piping sizeLiquid linemm (⌀ inch)ø22.22 (7/8”)
Refrigerant piping sizeGas linemm (⌀ inch)ø41.28(1·5/8")
Refrigerant piping sizeOil equalizationmm (⌀ inch)ø12.7 (1/2")
Capacity connection%50~150
Number of connectable indoor units80
SEER / SCOP (Outdoor unit)7.63 / 4.63
The data are measured under the following conditions (ISO-T1, H1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
SEER/SCOP are based on EN14825:2018 and Commission regulation (EU) No.2016/2281. Temperature conditions for calculating SCOP are based on "Average climate".
Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
Refrigerant contained in the products is a fluorinated greenhouse gas listed in Regulation (EU) No 517/2014.
When connecting the indoor unit type FDK, FDFL, FDFU or FDFW series, limit the connectable capacity not higher than 130%.