FDC155KXZES1

VRF Outdoor Unit

FDC155KXZES1

Micro Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 15.5kW
R410A

Nominal horse power 6HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max Current A 13.5
Nominal capacity Cooling kW 15.5
Heating 15.5
Electrical characteristics
Power Consumption
Cooling kW 5.20
Heating 4.28
Exterior dimensions HxWxD mm 845x970x370
Sound pressure level Cooling/Heating dB(A) 54/57
Net Weight kg 87
Refrigerant Type / GWP R410A / 2088
Refrigerant Charge kg/TCO2Eq 5.0 / 10.44
Refrigerant piping size Liquid line mm(in) ø9.52(3/8")
Refrigerant piping size Gas line mm(in) ø15.88(5/8")
Capacity connection % 80~150
Number of connectable indoor units 10 *
SEER / SCOP (Outdoor unit) 7.21 / 4.55
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.