FDC1450KXZRE1

VRF Outdoor Unit

FDC1450KXZRE1

Heat Recovery VRF Outdoor Unit

Nominal cooling capacity of 145.0kW

Combination (FDC) 475KXZRE1 + 475KXZRE1 + 500KXZRE1
Nominal horse power 52HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 24
Max Current A 121.8
Nominal capacity Cooling kW 145.0
Heating 145.0
Electrical characteristics
Power Consumption
Cooling kW 44.83
Heating 35.33
Exterior dimensions HxWxD mm 2048x4050x720
Net Weight kg 1230
Refrigerant charge R410A kg 11.5x3
Refrigerant piping size Liquid line mm(in) ø19.05(3/4”)
Refrigerant piping size Suction Gas line mm(in) ø38.1(1 1/2”)[ø34.92(1 3/8”)]
Refrigerant piping size Discharge Gas line mm(in) ø31.75(1 1/4”)[ø28.58(1 1/8”)]
Capacity connection % 50~130
Number of connectable indoor units 80
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.