FDC1000KXZWE1

VRF Outdoor Unit

FDC1000KXZWE1

Water Cooled Heat Pump VRF Outdoor Unit

Nominal cooling capacity of 100.0kW

Combination (FDC) 335KXZWE1 + 335KXZWE1 + 335KXZWE1
Nominal horse power 36HP
Power source 3 Phase 380-415V, 50Hz
Nominal capacity Cooling kW 100
Heating 112
Power Consumption Cooling kW 24.3
Heating 18.8
EER Cooling 4.1
COP Heating 6.0
Exterior dimensions HxWxD mm (1100x780x550)x3
Sound pressure level Cooling/Heating dB(A) 57
Net Weight kg 185x3
The data is based on the rating condition:
Cooling: Indoor temp. of 27 °C DB,19 °C WB, and heat source unit inlet water temp. of 30 °C, water flow rate 96 L/min
Heating: Indoor temp. of 20 °C DB,15 °C WB, and heat source unit inlet water temp. of 20 °C, water flow rate 96 L/min