Indoor unit | SRK71ZR-W | ||||
Outdoor unit | SRC71ZR-W | ||||
Power source | 1Phase, 220 - 240, 50Hz | ||||
Nominal cooling capacity (Min~Max) | kW | 7.1 (2.3~7.8) | |||
Nominal heating capacity (Min~Max) | kW | 8.0 (2.0~10.8) | |||
Power consumption | Cooling/Heating | kW | 1.93 / 1.95 | ||
EER/COP | Cooling/Heating | 3.68 / 4.10 | |||
Max. running current | A | 17 | |||
Sound power level | Indoor | Cooling/Heating | dB(A) | 57 / 60 | |
Outdoor | Cooling/Heating | 63 / 63 | |||
Sound pressure level | Indoor | Cooling (Hi/Me/Lo/Ulo) | 44 / 41 / 37 / 25 | ||
Heating (Hi/Me/Lo/Ulo) | 46 / 39 / 35 / 28 | ||||
Outdoor | Cooling/Heating | 53 / 51 | |||
Air flow | Indoor | Cooling (Hi/Me/Lo/Ulo) | m3/min | 20.5 / 18.6 / 16.2 / 10.4 | |
Heating (Hi/Me/Lo/Ulo) | 25.0 / 19.8 / 17.3 / 13.3 | ||||
Outdoor | Cooling/Heating | 55 / 43.5 | |||
Exterior Dimensions | Indoor | Height x Width x Depth | mm | 339 x 1197 x 262 | |
Outdoor | 750 x 880(+88) x 340 | ||||
Net weight | Indoor / Outdoor | kg | 15.5 / 56.0 | ||
Refrigerant | Type/GWP | R32 / 675 | |||
Refrigerant | Charge | kg/TCO2Eq | 1.5 / 1.013 | ||
Refrigerant piping size | Liquid/Gas | ø inch | 6.35(1/4") / 15.88(5/8") | ||
Refrigerant line (one way) length | m | Max. 30 | |||
Vertical height differences | Outdoor is higher/lower | m | Max. 20 / Max. 20 | ||
Outdoor operating temperature range | Cooling | °C | -15~46 | ||
Heating | -15~24 | ||||
Clean filter | Allergen Clear Filter x 1, Photocatalytic Washable Deodorizing Filter x 1 | ||||
Energy Class (Cooling/Heating) | A++/A+ | ||||
SEER | 7.40 | ||||
SCOP (Average climate) | 4.50 | ||||
Pdesign (cooling/heating(@-10°C)) | kW | 7.10/6.60 | |||
Annual Electricity Consumption (cooling/heating) | kWh/a | 337/2055 | |||
Designated Heating Season | Average |
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281