SRK63ZR-W / SRC63ZR-W

6.3 (1.2~7.4) Wall Mounted Single Split RAC

SRK63ZR-W / SRC63ZR-W

Wall Mounted : 6.3 (1.2~7.4)

Indoor Unit - SRK63ZR-W / Outdoor Unit - SRC63ZR-W
Nominal cooling capacity of 6.3kW

R32
  • SRK63ZR-W
  • SRK63ZR-W

    Indoor Unit : SRK63ZR-W

    SRC63ZR-W

    Outdoor Unit : SRC63ZR-W

  • SRC63ZR-W
Indoor unitSRK63ZR-W
Outdoor unitSRC63ZR-W
Power source1Phase, 220 - 240, 50Hz
Nominal cooling capacity (Min~Max)kW6.3 (1.2~7.4)
Nominal heating capacity (Min~Max)kW7.1 (0.8~9.3)
Power consumptionCooling/HeatingkW1.63 / 1.64
EER/COPCooling/Heating3.87 / 4.33
Max. running currentA14.5
Sound power
level
IndoorCooling/HeatingdB(A)56 / 58
OutdoorCooling/Heating64 / 65
Sound pressure
level
IndoorCooling (Hi/Me/Lo/Ulo)44 / 39 / 35 / 25
Heating (Hi/Me/Lo/Ulo)44 / 38 / 34 / 28
OutdoorCooling/Heating54 / 54
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min20.5 / 18.1 / 15.7 / 10.4
Heating (Hi/Me/Lo/Ulo)22.5 / 19.0 / 16.5 / 13.1
OutdoorCooling/Heating41.5 / 41.5
Exterior DimensionsIndoorHeight x Width x Depthmm339 x 1197 x 262
Outdoor640 x 800(+71) x 290
Net weightIndoor / Outdoorkg15.5 / 45.0
RefrigerantType/GWPR32 / 675
RefrigerantChargekg/TCO2Eq1.25 / 0.844
Refrigerant piping sizeLiquid/Gasø inch6.35(1/4") / 12.7(1/2")
Refrigerant line (one way) lengthmMax. 30
Vertical height differencesOutdoor is higher/lowermMax. 20 / Max. 20
Outdoor operating
temperature range
Cooling°C-15~46
Heating-15~24
Clean filterAllergen Clear Filter x 1, Photocatalytic Washable Deodorizing Filter x 1
Energy Class (Cooling/Heating)A++/A++
SEER8.10
SCOP (Average climate)4.70
Pdesign (cooling/heating(@-10°C))kW6.30/5.40
Annual Electricity Consumption (cooling/heating)kWh/a273/1608
Designated Heating SeasonAverage
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281