SRK50ZT-WFT / SRC50ZT-W(B)

5.0(1.3~ 5.4) Wall Mounted Single Split RAC

SRK50ZT-WFT / SRC50ZT-W(B)

Wall Mounted : 5.0(1.3~ 5.4)

Indoor Unit - SRK50ZT-WFT / Outdoor Unit - SRC50ZT-W(B)
Nominal cooling capacity of 5.0kW

R32
  • SRK50ZT-WFT
  • SRK50ZT-WFT

    Indoor Unit : SRK50ZT-WFT

    SRC50ZT-W(B)

    Outdoor Unit : SRC50ZT-W(B)

  • SRC50ZT-W(B)
Indoor unitSRK50ZT-WFT
Outdoor unitSRC50ZT-W(B)
Power source1Phase, 220 - 240, 50Hz
Nominal cooling capacity (Min~Max)kW5.0(1.3~ 5.4)
Nominal heating capacity (Min~Max)kW5.8(1.3~6.4)
Power consumptionCooling/HeatingkW1.43 / 1.48
EER/COPCooling/Heating3.50 / 3.92
Max. running currentA14.5
Sound power
level
IndoorCooling/HeatingdB(A)59 / 59
OutdoorCooling/Heating63 / 63
Sound pressure
level
IndoorCooling (Hi/Me/Lo/Ulo)45 / 36 / 29 / 22
Heating (Hi/Me/Lo/Ulo)44 / 37 / 31 / 24
OutdoorCooling/Heating50 / 51
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min13.3 / 10.0 / 7.6 / 5.7
Heating (Hi/Me/Lo/Ulo)13.5 / 10.6 / 8.8 / 6.6
OutdoorCooling/Heating29.8 / 29.8
Exterior DimensionsIndoorHeight x Width x Depthmm290 x 870 x 230
Outdoor595 x 780(+62) x 290
Net weightIndoor / Outdoorkg11.0 / 33.0
RefrigerantType/GWPR32 / 675
RefrigerantChargekg/TCO2Eq0.83 / 0.56
Refrigerant piping sizeLiquid/Gasmm (⌀ inch)6.35(1/4") / 12.7(1/2")
Refrigerant line (one way) lengthmMax. 25
Vertical height differencesOutdoor is higher/lowermMax. 20 / Max. 20
Outdoor operating
temperature range
Cooling°C-15~50
Heating-20~24
Clean filterAllergen Clear Filter x 1, Photocatalytic Washable Deodorizing Filter x 1
Energy Class (Cooling/Heating)A++/A++
SEER7.5
SCOP (Average climate)4.7
Pdesign (cooling/heating(@-10°C))kW5.00/3.80
Annual Electricity Consumption (cooling/heating)kWh/a234/1133
Designated Heating SeasonAverage
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
• SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281