SRK35ZSP-W / SRC35ZSP-W

3.2(0.9~3.7) Wall Mounted Single Split RAC

SRK35ZSP-W / SRC35ZSP-W

Wall Mounted : 3.2(0.9~3.7)

Indoor Unit - SRK35ZSP-W / Outdoor Unit - SRC35ZSP-W
Nominal cooling capacity of 3.5kW

R32
  • SRK35ZSP-W
  • SRK35ZSP-W

    Indoor Unit : SRK35ZSP-W

    SRC35ZSP-W

    Outdoor Unit : SRC35ZSP-W

  • SRC35ZSP-W
Indoor unit SRK35ZSP-W
Outdoor unit SRC35ZSP-W
Power source 1 Phase, 220 - 240V, 50Hz
Nominal cooling capacity (Min~Max) kW 3.2(0.9~3.7)
Nominal heating capacity (Min~Max) kW 3.6(1.0~4.6)
Power consumption Cooling/Heating kW 0.910 / 0.930
EER/COP Cooling/Heating 3.52 / 3.87
Max. running current A 9
Sound power
level
Indoor Cooling/Heating dB(A) 58 / 58
Outdoor Cooling/Heating 59 / 60
Sound pressure
level
Indoor Cooling (Hi/Me/Lo/Ulo) 45 / 36 / 23
Heating (Hi/Me/Lo/Ulo) 44 / 36 / 28
Outdoor Cooling/Heating 48 / 48
Air flow Indoor Cooling (Hi/Me/Lo/Ulo) m3/min 9.5 / 6.8 / 4.2
Heating (Hi/Me/Lo/Ulo) 9.6 / 7.4 / 5.5
Outdoor Cooling/Heating 22.8 / 22.0
Exterior Dimensions Indoor Height x Width x Depth mm 267 x 783 x 210
Outdoor 540 x 645(+57) x 275
Net weight Indoor / Outdoor kg 7.0 / 28.5
Refrigerant Type/GWP R32 / 675
Refrigerant Charge kg/TCO2Eq 0.68 / 0.459
Refrigerant piping size Liquid/Gas ø mm 6.35(1/4") / 9.52(3/8")
Refrigerant line (one way) length m Max. 15
Vertical height differences Outdoor is higher/lower m Max. 10 / Max. 10
Outdoor operating
temperature range
Cooling °C -15~46
Heating -15~24
Clean filter -
Energy Class (Cooling/Heating) A++/A+
SEER 7.30
SCOP (Average climate) 4.40
Pdesign (cooling/heating(@-10°C)) kW 3.20/3.00
Annual Electricity Consumption (cooling/heating) kWh/a 155/955
Designated Heating Season Average
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281