SRK35ZSP-S / SRC35ZSP-S

3.2(0.9~3.5) Wall Mounted Single Split RAC

SRK35ZSP-S / SRC35ZSP-S

Wall Mounted : 3.2(0.9~3.5)

Indoor Unit - SRK35ZSP-S / Outdoor Unit - SRC35ZSP-S
Nominal cooling capacity of 3.5kW

R410A
  • SRK35ZSP-S
  • SRK35ZSP-S

    Indoor Unit : SRK35ZSP-S

    SRC35ZSP-S

    Outdoor Unit : SRC35ZSP-S

  • SRC35ZSP-S
Indoor unitSRK35ZSP-S
Outdoor unitSRC35ZSP-S
Power source1Phase, 220 - 240, 50Hz
Nominal cooling capacity (Min~Max)kW3.2(0.9~3.5)
Nominal heating capacity (Min~Max)kW3.6(0.9~4.3)
Power consumptionCooling/HeatingkW0.995 / 0.995
EER/COPCooling/Heating3.22 / 3.62
Max. running currentA9
Sound power
level
IndoorCooling/HeatingdB(A)59 / 58
OutdoorCooling/Heating60 / 60
Sound pressure
level
IndoorCooling (Hi/Me/Lo/Ulo)45 / 36 / 23
Heating (Hi/Me/Lo/Ulo)44 / 36 / 28
OutdoorCooling/Heating47 / 48
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min9.5 / 6.8 / 4.2
Heating (Hi/Me/Lo/Ulo)9.6 / 7.4 / 5.5
OutdoorCooling/Heating25.4 / 20.5
Exterior DimensionsIndoorHeight x Width x Depthmm267 x 783 x 210
Outdoor540 x 645(+57) x 275
Net weightIndoor / Outdoorkg7.0 / 27.0
RefrigerantType/GWPR410A / 2088
RefrigerantChargekg/TCO2Eq0.81 / 1.691
Refrigerant piping sizeLiquid/Gasø inch6.35(1/4") / 9.52(3/8")
Refrigerant line (one way) lengthmMax. 15
Vertical height differencesOutdoor is higher/lowermMax. 10 / Max. 10
Outdoor operating
temperature range
Cooling°C-15~46
Heating-15~24
Clean filter-
Energy Class (Cooling/Heating)A++/A+
SEER6.15
SCOP (Average climate)4.00
Pdesign (cooling/heating(@-10°C))kW3.20/3.00
Annual Electricity Consumption (cooling/heating)kWh/a183/1052
Designated Heating SeasonAverage
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281