Power source 1Phase, 220 - 240, 50Hz
Nominal cooling capacity (Min~Max) kW 2.5(0.9~2.8)
Nominal heating capacity (Min~Max) kW 2.8(0.8~3.9)
Power consumption Cooling/Heating kW 0.78 / 0.755
EER/COP Cooling/Heating 3.21/3.71
Max. running current A 9
Sound power
level
Indoor Cooling/Heating dB(A) 58 / 57
Outdoor Cooling/Heating 58 / 59
Sound pressure
level
Indoor Cooling (Hi/Me/Lo/Ulo) 45 / 34 / 23
Heating (Hi/Me/Lo/Ulo) 43 / 34 / 26
Outdoor Cooling/Heating 47 / 45
Air flow Indoor Cooling (Hi/Me/Lo/Ulo) m3/min 10.0 / 7.3 / 4.2
Heating (Hi/Me/Lo/Ulo) 9.5 / 7.3 / 5.2
Outdoor Cooling/Heating 26.0 / 19.7
Exterior Dimensions Indoor Height x Width x Depth mm 267 x 783 x 210
Outdoor 540 x 645(+57) x 275
Net weight Indoor / Outdoor kg 7.0 / 25.0
Refrigerant Type/GWP R410A / 2088
Refrigerant Charge kg/TCO2Eq 0.655 / 1.368
Refrigerant piping size Liquid/Gas ø mm 6.35(1/4") / 9.52(3/8")
Refrigerant line (one way) length m Max. 15
Vertical height differences Outdoor is higher/lower m Max. 10 / Max. 10
Outdoor operating
temperature range
Cooling °C -15~46
Heating -15~24
Clean filter -
Energy Class (Cooling/Heating) A/A
SEER 5.50
SCOP (Average climate) 3.80
Pdesign (cooling/heating(@-10°C)) kW 2.50/2.80
Annual Electricity Consumption (cooling/heating) kWh/a 160/1033
Designated Heating Season Average
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281