SRK20ZT-WA / SRC20ZT-WA

2.0 (0.9~3.0) Wall Mounted Single Split RAC

SRK20ZT-WA / SRC20ZT-WA

Wall Mounted : 2.0 (0.9~3.0)

Indoor Unit - SRK20ZT-WA / Outdoor Unit - SRC20ZT-WA
Nominal cooling capacity of 2.0kW

  • Nordic Model
  • Drain pan heater equipped
R32
  • SRK20ZT-WA
  • SRK20ZT-WA

    Indoor Unit : SRK20ZT-WA

    SRC20ZT-WA

    Outdoor Unit : SRC20ZT-WA

  • SRC20ZT-WA
Indoor unitSRK20ZT-WA
Outdoor unitSRC20ZT-WA
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max)kW2.0 (0.9~3.0)
Nominal heating capacity (Min~Max)kW2.7 (0.9~4.6)
Power consumptionCooling/HeatingkW0.38 / 0.55
EER/COPCooling/Heating5.26 / 4.91
Max. running currentA9
Sound power
level
IndoorCooling/HeatingdB(A)48 / 50
OutdoorCooling/Heating57 / 58
Sound pressure
level
IndoorCooling (Hi/Me/Lo/Ulo)34 / 25 / 22 / 19
Heating (Hi/Me/Lo/Ulo)36 / 29 / 23 / 19
OutdoorCooling/Heating45 / 45
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min9.3 / 7.0 / 5.9 / 5.0
Heating (Hi/Me/Lo/Ulo)10.0 / 8.5 / 6.5 / 5.9
OutdoorCooling/Heating27.8 / 22.1
Exterior DimensionsIndoorHeight x Width x Depthmm290 × 870 × 230
Outdoor540 × 780 (+62) × 290
Net weightIndoor / Outdoorkg9.5 / 34.5
RefrigerantType/GWPR32/675
RefrigerantChargekg/TCO2Eq0.78kg
Refrigerant piping sizeLiquid/Gasmm (⌀ inch)6.35(1/4") / 9.52(3/8")
Refrigerant line (one way) lengthm3 - 20
Vertical height differencesOutdoor is higher/lowermMax.10 / Max.10
Outdoor operating
temperature range
Cooling°C-15~46 ̊C
Heating-15~24 ̊C
Clean filterAllergen Clear Filter x 1, Photocatalytic Washable Deodorizing Filter x 1
Energy Class (Cooling/Heating)A+++/A++
SEER9.00
SCOP (Average climate)4.90
Pdesign (cooling/heating(@-10°C))kW2.00/2.60
Annual Electricity Consumption (cooling/heating)kWh/a78/743
Designated Heating SeasonAverage
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.