SRK20ZSX-S / SRC20ZSX-S

2.0 (0.9~3.2) Wall Mounted Single Split RAC

SRK20ZSX-S / SRC20ZSX-S

Wall Mounted : 2.0 (0.9~3.2)

Indoor Unit - SRK20ZSX-S / Outdoor Unit - SRC20ZSX-S
Nominal cooling capacity of 2.0kW

R410A
  • SRK20ZSX-S
  • SRK20ZSX-S

    Indoor Unit : SRK20ZSX-S

    SRC20ZSX-S

    Outdoor Unit : SRC20ZSX-S

  • SRC20ZSX-S
Indoor unitSRK20ZSX-S
Outdoor unitSRC20ZSX-S
Power source1Phase, 220 - 240, 50Hz
Nominal cooling capacity (Min~Max)kW2.0 (0.9~3.2)
Nominal heating capacity (Min~Max)kW2.7 (0.8~5.3)
Power consumptionCooling/HeatingkW0.32 / 0.47
EER/COPCooling/Heating6.25 / 5.74
Max. running currentA9
Sound power
level
IndoorCooling/HeatingdB(A)53 / 53
OutdoorCooling/Heating56 / 58
Sound pressure
level
IndoorCooling (Hi/Me/Lo/Ulo)38 / 31 / 24 / 19
Heating (Hi/Me/Lo/Ulo)38 / 32 / 25 / 19
OutdoorCooling/Heating43 / 44
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min11.3 / 9.1 / 6.0 / 5.0
Heating (Hi/Me/Lo/Ulo)12.2 / 10.3 / 7.2 / 5.4
OutdoorCooling/Heating31.0 / 31.0
Exterior DimensionsIndoorHeight x Width x Depthmm305 x 920 x 220
Outdoor640 x 800(+71) x 290
Net weightIndoor / Outdoorkg13.0 / 43.0
RefrigerantType/GWPR410A / 2088
RefrigerantChargekg/TCO2Eq1.45 / 3.028
Refrigerant piping sizeLiquid/Gasø mm6.35(1/4") / 9.52(3/8")
Refrigerant line (one way) lengthmMax.25
Vertical height differencesOutdoor is higher/lowermMax.15 / Max.15
Outdoor operating
temperature range
Cooling°C-15~46
Heating-20~24
Clean filterAllergen Clear Filter x 1, Photocatalytic Washable Deodorizing Filter x 1
Energy Class (Cooling/Heating)A+++/A+++
SEER9.50
SCOP (Average climate)5.20
Pdesign (cooling/heating(@-10°C))kW2.00/2.70
Annual Electricity Consumption (cooling/heating)kWh/a74/728
Designated Heating SeasonAverage
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281