SRK140VSXWTZSX

14.0 ( 3.5 ~ 16.0) Wall Mounted Multi Split PAC

SRK140VSXWTZSX

Wall Mounted : 14.0 ( 3.5 ~ 16.0)

Indoor Unit - SRK50ZSX-W x 3 / Outdoor Unit - FDC140VSX-W
Nominal cooling capacity of 14.0kW

R32
  • SRK50ZSX-W x 3
  • SRK50ZSX-W x 3

    Indoor Unit : SRK50ZSX-W x 3

    FDC140VSX-W

    Outdoor Unit : FDC140VSX-W

  • FDC140VSX-W
Indoor unit SRK50ZSX-W x 3
Outdoor unit FDC140VSX-W
Power source 3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min-Max) kW 14.0 ( 3.5 ~ 16.0)
Nominal heating capacity (Min-Max) kW 16.0 ( 2.7 ~ 20.0 )
Power Consumption Cooling/Heating kW 4.03 / 4.04
EER/COP Cooling/Heating kW 3.48 / 3.96
Inrush current A 5
Max. current A 14
Sound power level*1 Indoor*3 Cooling/Heating dB(A) 59 / 62
Outdoor Cooling/Heating 69 / 71
Sound pressure
level*1
Indoor*3 Cooling (P-Hi/Hi/Me/Lo) 44 / 39 / 31 / 22
Heating (P-Hi/Hi/Me/Lo) 46 / 41 / 33 / 23
Outdoor Cooling/Heating 54 / 54
Air flow Indoor*3 Cooling (P-Hi/Hi/Me/Lo) m3/min 14.3 / 12.4 / 7.8 / 5.4
Heating (P-Hi/Hi/Me/Lo) 17.3 / 14.3 / 9.8 / 6.2
Outdoor Cooling/Heating 100 / 100
Exterior
dimensions
Indoor HeightxWidthxDepth mm 305 x 920 x 220
Outdoor mm 1,300 x 970 x 370
Net weight Indoor/Outdoor kg 13 / 99
Refrigerant Type GWP R32/675
Ref.piping size Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.50 / Max.15
Outdoor operating temperature range Cooling*2 °C -15~50
Heating °C -20~20
Air filter, Q'ty Polypropylene net x 2(washable)
Remote control (option) wired:RC-EX3A, RC-E5, RCH-E3 & Interface kit:SC-BIKN2-E
The data is measured under the following conditions (ISO-T1, -H1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions
  2. : If a cooling operation is conducted when the outdoor air temperature is —5°C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind, if wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down