SRK140VSAWPZR

13.6 ( 5.0 ~ 14.5 ) Wall Mounted Multi Split PAC

SRK140VSAWPZR

Wall Mounted : 13.6 ( 5.0 ~ 14.5 )

Indoor Unit - SRK71ZR-W x 2 / Outdoor Unit - FDC140VSA-W
Nominal cooling capacity of 13.6kW

R32
  • SRK71ZR-W x 2
  • SRK71ZR-W x 2

    Indoor Unit : SRK71ZR-W x 2

    FDC140VSA-W

    Outdoor Unit : FDC140VSA-W

  • FDC140VSA-W
Indoor unit SRK71ZR-W x 2
Outdoor unit FDC140VSA-W
Power source 3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min-Max) kW 13.6 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min-Max) kW 15.5 ( 4.0 ~ 16.5 )
Power Consumption Cooling/Heating kW 4.26 / 4.03
EER/COP Cooling/Heating kW 3.19 / 3.85
Inrush current A 5
Max. current A 15
Sound power level*1 Indoor*3 Cooling/Heating dB(A) 57 / 60
Outdoor Cooling/Heating 72 / 73
Sound pressure
level*1
Indoor*3 Cooling (P-Hi/Hi/Me/Lo) 44 / 41 / 37 / 25
Heating (P-Hi/Hi/Me/Lo) 46 / 39 / 35 / 28
Outdoor Cooling/Heating 56 / 58
Air flow Indoor*3 Cooling (P-Hi/Hi/Me/Lo) m3/min 20.5 / 18.6 / 16.2 / 10.4
Heating (P-Hi/Hi/Me/Lo) 25.0 / 19.8 / 17.3 / 13.3
Outdoor Cooling/Heating 75 / 73
Exterior
dimensions
Indoor HeightxWidthxDepth mm 339 x 1197 x 262
Outdoor mm 845 x 970 x 370
Net weight Indoor/Outdoor kg 15.5 / 78
Refrigerant Type GWP R32/675
Ref.piping size Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.50 / Max.15
Outdoor operating temperature range Cooling*2 °C -15~50
Heating °C -20~20
Air filter, Q'ty Polypropylene net x 2(washable)
Remote control (option) wired:RC-EX3A, RC-E5, RCH-E3 Interface kit:SC-BIKN2-E
The data is measured under the following conditions (ISO-T1, -H1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions
  2. : If a cooling operation is conducted when the outdoor air temperature is —5°C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind, if wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down