SRK100VNXPZSX

10.0 ( 4.0 ~ 11.2 ) Wall Mounted Multi Split PAC

SRK100VNXPZSX

Wall Mounted : 10.0 ( 4.0 ~ 11.2 )

Indoor Unit - SRK50ZSX-W x 2 / Outdoor Unit - FDC100VNX
Nominal cooling capacity of

  • SRK50ZSX-W x 2
  • SRK50ZSX-W x 2

    Indoor Unit : SRK50ZSX-W x 2

    FDC100VNX

    Outdoor Unit : FDC100VNX

  • FDC100VNX
Indoor unit SRK50ZSX-W x 2
Outdoor unit FDC100VNX
Power source 1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min-Max) kW 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min-Max) kW 11.2 ( 4.0 ~ 12.5 )
Power Consumption Cooling/Heating kW 2.66 / 2.60
EER/COP Cooling/Heating kW 3.76 / 4.31
Inrush current A 5
Max. current A 24
Sound power level*1 Indoor*3 Cooling/Heating dB(A) 59 / 62
Sound power level*1 Outdoor Sound power level dB(A) 70 / 70
Sound pressure level*1 Indoor*3 Cooling (P-Hi/Hi/Me/Lo) dB(A) 44 / 39 / 31 / 22
Indoor Heating (P-Hi/Hi/Me/Lo) dB(A) 46 / 41 / 33 / 23
Outdoor Cooling/Heating dB(A) 48 / 50
Air flow Indoor*3 Cooling (P-Hi/Hi/Me/Lo) m3/min 14.3 / 12.4 / 7.8 / 5.4
Indoor Heating (P-Hi/Hi/Me/Lo) m3/min 17.3 / 14.3 / 9.8 / 6.2
Outdoor Cooling/Heating m3/min 100 / 100
Exterior
dimensions
Indoor HeightxWidthxDepth mm 305 x 920 x 220
Outdoor mm 1,300 x 970 x 370
Net weight Indoor/Outdoor kg 13 / 105
Refrigerant charge kg/TCO2Eq 4.5/9.396
Refrigerant Type GWP R410A/1975
Ref.piping size Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operating temperature range Cooling*2 °C -15~43
Heating °C -20~20
Air filter, Q'ty Polypropylene net x 2(washable)
Remote control (option) wired:RC-EX3A, RC-E5, RCH-E3 & Interface kit:SC-BIKN2-E
Energy Class (Cooling/Heating) A++/A+
SEER 6.11
SCOP (Average climate) 4.16
Pdesign (cooling/heating(@-10°C)) 10.0/10.4
Annual Electricity Consumption 574/3504
Designated Heating Season Average
The data is measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
*1: Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions
*2: If a cooling operation is conducted when the outdoor air temperature is —5°C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind, if wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down
*3: The values are for one indoor unit operation. (Multi system only)