SRF50ZSX-W / SRC50ZSX-W2

5.0 ( 1.1 (Min.) - 5.6 (Max.)) Floor Standing Single Split RAC

SRF50ZSX-W / SRC50ZSX-W2

Floor Standing : 5.0 ( 1.1 (Min.) - 5.6 (Max.))

Indoor Unit - SRF50ZSX-W / Outdoor Unit - RC50ZSX-W2
Nominal cooling capacity of 5.0kW

R32
  • SRF50ZSX-W
  • SRF50ZSX-W

    Indoor Unit : SRF50ZSX-W

    RC50ZSX-W2

    Outdoor Unit : RC50ZSX-W2

  • RC50ZSX-W2
Indoor unitSRF50ZSX-W
Outdoor unitRC50ZSX-W2
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max)kW5.0 ( 1.1 (Min.) - 5.6 (Max.))
Nominal heating capacity (Min~Max)kW6.0 ( 0.8 (Min.) - 7.4 (Max.))
Power consumptionCooling/HeatingkW1.32 ( 0.19 - 1.90 ) / 1.58 ( 0.19 - 2.34 )
EER/COPCooling/Heating3.79 / 3.80
Max. running currentA15
Sound power
level
IndoorCooling/HeatingdB(A)58 / 58
OutdoorCooling/Heating63 / 62
Sound pressure
level
IndoorCooling (Hi/Me/Lo/Ulo)46 / 38 / 33 / 28
Heating (Hi/Me/Lo/Ulo)46 / 41 / 38 / 32
OutdoorCooling/Heating51 / 51
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min11.5 / 9.6 / 7.4 / 6.6
Heating (Hi/Me/Lo/Ulo)12.0 / 10.0 / 9.4 / 7.6
OutdoorCooling/Heating39.0 / 33.0
Exterior DimensionsIndoorHeight x Width x Depthmm600 x 860 x 238
Outdoor640 x 800 (+71) x 290
Net weightIndoor / Outdoorkg19.0 / 45.0
RefrigerantType/GWPR32/675
RefrigerantChargekg/TCO2Eq1.30 / 0.878
Refrigerant piping sizeLiquid/Gasø mm6.35 (1/4") / 12.7 (1/2")
Refrigerant line (one way) lengthmMax. 30 [15]
Vertical height differencesOutdoor is higher/lowermMax. 20 / Max. 20
Outdoor operating
temperature range
Cooling°C-20~24
Heating
Clean filterAllergen Clean Filter x 1 Photocatalytic Washable Deodorising Filter x 1
Energy Class (Cooling/Heating)A++/A++
SEER7.50
SCOP (Average climate)4.60
• The data is measured under the following conditions(ISO-T1, H1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
• Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
• 'tonne(s) of CO2 equivalent' means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
*SEER/SCOP are based on EN14825:2016 and Commission regulation (EU) No.2016/2281