FDUM250VSAPVH

24.0 ( 6.9 ~ 28.0 ) Low Static Pressure Duct Connected Multi Split PAC

FDUM250VSAPVH

Low Static Pressure Duct Connected : 24.0 ( 6.9 ~ 28.0 )

Indoor Unit - FDUM125VH x 2 / Outdoor Unit - FDC250VSA
Nominal cooling capacity of 25.0kW

R410A
  • FDUM125VH x 2
  • FDUM125VH x 2

    Indoor Unit : FDUM125VH x 2

    FDC250VSA

    Outdoor Unit : FDC250VSA

  • FDC250VSA
Indoor unit FDUM125VH x 2
Outdoor unit FDC250VSA
Power source 3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min-Max) kW 24.0 ( 6.9 ~ 28.0 )
Nominal heating capacity (Min-Max) kW 27.0 ( 5.5 ~ 31.5 )
Power Consumption Cooling/Heating kW 8.33 / 7.52
EER/COP Cooling/Heating kW 2.88 / 3.59
Inrush current A 5
Max. current A 24
Sound power level*1 Indoor*3 Cooling/Heating dB(A) 67 / 67
Outdoor Cooling/Heating 73 / 75
Sound pressure
level*1
Indoor*3 Cooling (P-Hi/Hi/Me/Lo) 45 / 40 / 34 / 29
Heating (P-Hi/Hi/Me/Lo) 45 / 40 / 34 / 29
Outdoor Cooling/Heating 59 / 62
Air flow Indoor*3 Cooling (P-Hi/Hi/Me/Lo) m3/min 39 / 32 / 26 / 20
Heating (P-Hi/Hi/Me/Lo) 39 / 32 / 26 / 20
Outdoor Cooling/Heating 143 / 151
External static pressure Pa Standard:60 Max:100
Exterior
dimensions
Indoor HeightxWidthxDepth mm 280 x 1,370 x 740
Outdoor mm 1,505 x 970 x 370
Net weight Indoor/Outdoor kg 54 / 143
Refrigerant Type GWP R410A/2088
Ref.piping size Liquid/Gas ømm 12.7(1/2") / 22.22(7/8")
Refrigerant line (one way) length m Max.70
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operating temperature range Cooling*2 °C -15~50
Heating °C -15~20
Air filter, Q'ty (Option) Filter kit : UM-FL3EF
Remote control (option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
The data is measured under the following conditions (R32 : ISO-T1, -H1 /, R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions
  2. : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at external static pressure of 200Pa
  3. : If a cooling operation is conducted when the outdoor air temperature is —5°C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind, if wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down
  4. : The values are for one indoor unit operation. (Multi system only)