FDUM200VSATVH

19.0 ( 5.2 ~ 22.4 ) Low Static Pressure Duct Connected Multi Split PAC

FDUM200VSATVH

Low Static Pressure Duct Connected : 19.0 ( 5.2 ~ 22.4 )

Indoor Unit - FDUM71VH x 3 / Outdoor Unit - FDC200VSA
Nominal cooling capacity of 20.0kW

R410A
  • FDUM71VH x 3
  • FDUM71VH x 3

    Indoor Unit : FDUM71VH x 3

    FDC200VSA

    Outdoor Unit : FDC200VSA

  • FDC200VSA
Indoor unitFDUM71VH x 3
Outdoor unitFDC200VSA
Power source3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min-Max)kW19.0 ( 5.2 ~ 22.4 )
Nominal heating capacity (Min-Max)kW22.4 ( 3.3 ~ 25.0 )
Power ConsumptionCooling/HeatingkW6.46 / 6.15
EER/COPCooling/HeatingkW2.94 / 3.64
Inrush currentA5
Max. currentA22
Sound power level*1Indoor*3Cooling/HeatingdB(A)65 / 65
OutdoorCooling/Heating72 / 74
Sound pressure
level*1
Indoor*3Cooling (P-Hi/Hi/Me/Lo)38 / 33 / 29 / 25
Heating (P-Hi/Hi/Me/Lo)38 / 33 / 29 / 25
OutdoorCooling/Heating58 / 59
Air flowIndoor*3Cooling (P-Hi/Hi/Me/Lo)m3/min24 / 19 / 15 / 10
Heating (P-Hi/Hi/Me/Lo)24 / 19 / 15 / 10
OutdoorCooling/Heating135 / 135
External static pressurePaStandard:35 Max:100
Exterior
dimensions
IndoorHeightxWidthxDepthmm280 x 950 x 635
Outdoormm1,300 x 970 x 370
Net weightIndoor/Outdoorkg34 / 115
Refrigerant Type GWPR410A/2088
Ref.piping sizeLiquid/Gasømm9.52(3/8") / 22.22(7/8")
Refrigerant line (one way) lengthmMax.70
Vertical height differencesOutdoor is higher/lowermMax.30 / Max.15
Outdoor operating temperature rangeCooling*2°C-15~50
Heating°C-15~20
Air filter, Q'ty(Option) Filter kit : UM-FL2EF
Remote control (option)wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
The data is measured under the following conditions (R32 : ISO-T1, -H1 /, R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions
  2. : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at external static pressure of 200Pa
  3. : If a cooling operation is conducted when the outdoor air temperature is —5°C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind, if wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down
  4. : The values are for one indoor unit operation. (Multi system only)