×

FDU250VSAVG

24.0 ( 6.9 ~ 28.0) High Static Pressure Duct Connected Single Split PAC

FDU250VSAVG

High Static Pressure Duct Connected : 24.0 ( 6.9 ~ 28.0)

Indoor Unit - FDU250VG / Outdoor Unit - FDC250VSA
Nominal cooling capacity of 25.0kW

R410A
  • FDU250VG
  • FDU250VG

    Indoor Unit : FDU250VG

    FDC250VSA

    Outdoor Unit : FDC250VSA

  • FDC250VSA
Indoor unitFDU250VG
Outdoor unitFDC250VSA
Power source3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min~Max)kW24.0 ( 6.9 ~ 28.0)
Nominal heating capacity (Min~Max)kW27.0 ( 5.5 ~ 31.5 )
Power consumptionCooling/HeatingkW7.98 / 7.20
EER/COPCooling/Heating3.01 / 3.75
Inrush currentA5
Max. running currentA27
Sound power
level*1
Indoor *3Cooling/HeatingdB(A)75 / 75
OutdoorCooling/Heating73 / 75
Sound pressure
level*1
Indoor *3Cooling (Hi/Me/Lo/Ulo)52 / 50 / 47 / 45
Heating (Hi/Me/Lo/Ulo)52 / 50 / 47 / 45
OutdoorCooling/Heating59 / 62
Air flowIndoor *3Cooling (Hi/Me/Lo/Ulo)m3/min80 / 72 / 64 / 56
Heating (Hi/Me/Lo/Ulo)80 / 72 / 64 / 56
OutdoorCooling/Heating143 / 151
Available external static pressurePaStandard:72 Max:200
Exterior DimensionsIndoorHeight x Width x Depthmm379 x 1,600 x 893
Outdoor1,505 x 970 x 370
Net weightIndoor / Outdoorkg89 / 143
RefrigerantType/GWPR410A/2088
Refrigerant piping sizeLiquid/Gasø mm12.7(1/2") / 25.4(1")
Refrigerant line (one way) lengthmMax.70
Vertical height differencesOutdoor is higher/lowermMax.30 / Max.15
Outdoor operating
temperature range
Cooling*2°C-15~50
Heating-15~20
Air filter quantityProcure locally
Remote control (option)wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
SEER4.82
SCOP (Average climate)3.51
The data is measured under the following conditions (R32 : ISO-T1, -H1 /, R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at external static pressure of 200Pa
  3. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.