×

FDU200VSAVG

19.0 ( 5.2 ~ 22.4 ) High Static Pressure Duct Connected Single Split PAC

FDU200VSAVG

High Static Pressure Duct Connected : 19.0 ( 5.2 ~ 22.4 )

Indoor Unit - FDU200VG / Outdoor Unit - FDC200VSA
Nominal cooling capacity of 20.0kW

R410A
  • FDU200VG
  • FDU200VG

    Indoor Unit : FDU200VG

    FDC200VSA

    Outdoor Unit : FDC200VSA

  • FDC200VSA
Indoor unit FDU200VG
Outdoor unit FDC200VSA
Power source 3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min~Max) kW 19.0 ( 5.2 ~ 22.4 )
Nominal heating capacity (Min~Max) kW 22.4 ( 3.3 ~ 25.0 )
Power consumption Cooling/Heating kW 6.15 / 6.03
EER/COP Cooling/Heating 3.09 / 3.71
Inrush current A 5
Max. running current A 25
Sound power
level*1
Indoor *3 Cooling/Heating dB(A) 75 / 75
Outdoor Cooling/Heating 72 / 74
Sound pressure
level*1
Indoor *3 Cooling (Hi/Me/Lo/Ulo) 52 / 50 / 47 / 45
Heating (Hi/Me/Lo/Ulo) 52 / 50 / 47 / 45
Outdoor Cooling/Heating 58 / 59
Air flow Indoor *3 Cooling (Hi/Me/Lo/Ulo) m3/min 80 / 72 / 64 / 56
Heating (Hi/Me/Lo/Ulo) 80 / 72 / 64 / 56
Outdoor Cooling/Heating 135 / 135
Available external static pressure Pa Standard:72 Max:200
Exterior Dimensions Indoor Height x Width x Depth mm 379 x 1,600 x 893
Outdoor 1,300 x 970 x 370
Net weight Indoor / Outdoor kg 89 / 115
Refrigerant Type/GWP R410A/2088
Refrigerant piping size Liquid/Gas ø mm 9.52(3/8") / 25.4(1")
Refrigerant line (one way) length m Max.70
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operating
temperature range
Cooling*2 °C -15~50
Heating -15~20
Air filter quantity Procure locally
Remote control (option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
SEER 5.06
SCOP (Average climate) 3.52
The data is measured under the following conditions (R32 : ISO-T1, -H1 /, R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at external static pressure of 200Pa
  3. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.