FDU140VNXWVH

14.0 ( 3.5 ~ 16.0 ) High Static Pressure Duct Connected Single Split PAC

FDU140VNXWVH

High Static Pressure Duct Connected : 14.0 ( 3.5 ~ 16.0 )

Indoor Unit - FDU140VH / Outdoor Unit - FDC140VNX-W
Nominal cooling capacity of 14.0kW

R32
  • FDU140VH
  • FDU140VH

    Indoor Unit : FDU140VH

    FDC140VNX-W

    Outdoor Unit : FDC140VNX-W

  • FDC140VNX-W
Indoor unit FDU140VH
Outdoor unit FDC140VNX-W
Power source 1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max) kW 14.0 ( 3.5 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 16.0 ( 2.7 ~ 18.0 )
Power consumption Cooling/Heating kW 4.22 / 4.22
EER/COP Cooling/Heating 3.32 / 3.79
Inrush current A 5
Max. running current A 30
Sound power
level*1
Indoor *3 Cooling/Heating dB(A) 70 / 70
Outdoor Cooling/Heating 69 / 71
Sound pressure
level*1
Indoor *3 Cooling (Hi/Me/Lo/Ulo) 47 / 40 / 35 / 30
Heating (Hi/Me/Lo/Ulo) 47 / 40 / 35 / 30
Outdoor Cooling/Heating 54 / 54
Air flow Indoor *3 Cooling (Hi/Me/Lo/Ulo) m3/min 48 / 35 / 28 / 22
Heating (Hi/Me/Lo/Ulo) 48 / 35 / 28 / 22
Outdoor Cooling/Heating 100 / 100
Available external static pressure Pa Standard:60 Max:200
Exterior Dimensions Indoor Height x Width x Depth mm 280 x 1,370 x 740
Outdoor 1,300 x 970 x 370
Net weight Indoor / Outdoor kg 54 / 97
Refrigerant Type/GWP R32/675
Refrigerant piping size Liquid/Gas ø mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.50 / Max.15
Outdoor operating
temperature range
Cooling*2 °C -15~50
Heating -20~20
Air filter quantity Procure locally
Remote control (option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
SEER 5.79
SCOP (Average climate) 3.99
The data is measured under the following conditions (ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level become 5dB(A) higher at external static pressure of 200Pa
  3. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.