FDT71VNPVH

7.1 ( 1.4 ~ 7.1 ) Ceiling Cassette Single Split PAC

FDT71VNPVH

Ceiling Cassette : 7.1 ( 1.4 ~ 7.1 )

Indoor Unit - FDT71VH / Outdoor Unit - FDC71VNP
Nominal cooling capacity of 7.1kW

R410A
  • FDT71VH
  • FDT71VH

    Indoor Unit : FDT71VH

    FDC71VNP

    Outdoor Unit : FDC71VNP

  • FDC71VNP
Indoor unit FDT71VH
Outdoor unit FDC71VNP
Power source 1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 1.4 ~ 7.1 )
Nominal heating capacity (Min~Max) kW 7.1 ( 1.0 ~ 7.1 )
Power consumption Cooling/Heating kW 2.31 / 1.73
EER/COP Cooling/Heating 3.07 / 4.10
Inrush current A 5
Max. running current A 14.5
Sound power
level*1
Indoor Cooling/Heating dB(A) 59 / 60
Outdoor Cooling/Heating 67 / 67
Sound pressure
level*1
Indoor Cooling (Hi/Me/Lo/Ulo) 46 / 34 / 31 / 26
Heating (Hi/Me/Lo/Ulo) 46 / 34 / 31 / 26
Outdoor Cooling/Heating 54 / 54
Air flow Indoor Cooling (Hi/Me/Lo/Ulo) m3/min 28 / 18 / 15 / 12
Heating (Hi/Me/Lo/Ulo) 28 / 18 / 15 / 12
Outdoor Cooling/Heating 36 / 36
Exterior Dimensions Indoor Height x Width x Depth mm Unit: 236 x 840 x 840 Panel: 35 x 950 x 950
Outdoor 640 x 800(+71) x 290
Net weight Indoor / Outdoor kg 26(Unit:21 Standard Panel:5) / 45
Refrigerant Type/GWP R410A/2088
Refrigerant Charge kg/TCO2Eq 1.6/3.341
Refrigerant piping size Liquid/Gas ø mm 6.35(1/4") / 12.7(1/2")
Refrigerant line (one way) length m Max.30
Vertical height differences Outdoor is higher/lower m Max.20 / Max.20
Outdoor operating
temperature range
Cooling*2 °C -15~46
Heating -15~20
Panel T-PSA-5BW-E, T-PSAE-5BW-E (White) / T-PSA-5BB-E, T-PSAE-5BB-E (Black)
Air filter quantity Pocket Plastic net x 1(Washable)
Remote control (option) wired: RC-EX3A, RC-E5, RCH-E3 wireless: RCN-T-5BW-E2, RCN-T-5BB-E2
Energy Class (Cooling/Heating) A++/A+
SEER 6.14
SCOP (Average climate) 4.27
Pdesign (cooling/heating(@-10°C)) kW 7.1/5.7
Annual Electricity Consumption (cooling/heating) kWh/a 405/1867
Designated Heating Season Average
The data is measured under the following conditions (R32 : ISO-T1, -H1 /, R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.