FDT100VNPVH

10.0 ( 2.8 ~ 11.2 ) Ceiling Cassette Single Split PAC

FDT100VNPVH

Ceiling Cassette : 10.0 ( 2.8 ~ 11.2 )

Indoor Unit - FDT100VH / Outdoor Unit - FDC100VNP
Nominal cooling capacity of 10.0kW

R410A
  • FDT100VH
  • FDT100VH

    Indoor Unit : FDT100VH

    FDC100VNP

    Outdoor Unit : FDC100VNP

  • FDC100VNP
Indoor unitFDT100VH
Outdoor unitFDC100VNP
Power source1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max)kW10.0 ( 2.8 ~ 11.2 )
Nominal heating capacity (Min~Max)kW11.2 ( 2.5 ~ 12.5 )
Power consumptionCooling/HeatingkW2.76 / 2.84
EER/COPCooling/Heating3.62 / 3.94
Inrush currentA5
Max. running currentA21.0
Sound power
level*1
IndoorCooling/HeatingdB(A)62 / 62
OutdoorCooling/Heating70 / 70
Sound pressure
level*1
IndoorCooling (Hi/Me/Lo/Ulo)47 / 39 / 36 / 30
Heating (Hi/Me/Lo/Ulo)47 / 39 / 36 / 29
OutdoorCooling/Heating57 / 61
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min37 / 26 / 23 / 17
Heating (Hi/Me/Lo/Ulo)37 / 26 / 23 / 17
OutdoorCooling/Heating75 / 79
Exterior DimensionsIndoorHeight x Width x DepthmmUnit: 298 x 840 x 840 Panel: 35 x 950 x 950
Outdoor845 x 970 x 370
Net weightIndoor / Outdoorkg30(Unit:25 Standard Panel:5) / 70
RefrigerantType/GWPR410A/2088
RefrigerantChargekg/TCO2Eq2.55/5.324
Refrigerant piping sizeLiquid/Gasø mm9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) lengthmMax.30
Vertical height differencesOutdoor is higher/lowermMax.20 / Max.20
Outdoor operating
temperature range
Cooling*2°C-15~46
Heating-15~20
PanelT-PSA-5BW-E, T-PSAE-5BW-E (White) / T-PSA-5BB-E, T-PSAE-5BB-E (Black)
Air filter quantityPocket Plastic net x 1(Washable)
Remote control (option)wired: RC-EX3A, RC-E5, RCH-E3 wireless: RCN-T-5BW-E2, RCN-T-5BB-E2
Energy Class (Cooling/Heating)A++/A+
SEER6.78
SCOP (Average climate)4.53
Pdesign (cooling/heating(@-10°C))kW10.0/8.1
Annual Electricity Consumption (cooling/heating)kWh/a517/2506
Designated Heating SeasonAverage
The data is measured under the following conditions (R32 : ISO-T1, -H1 /, R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.