×

FDT100VNAWVH

10.0 ( 4.0 ~ 11.2 ) Ceiling Cassette Single Split PAC

FDT100VNAWVH

Ceiling Cassette : 10.0 ( 4.0 ~ 11.2 )

Indoor Unit - FDT100VH / Outdoor Unit - FDC100VNA-W
Nominal cooling capacity of 10.0kW

R32
  • FDT100VH
  • FDT100VH

    Indoor Unit : FDT100VH

    FDC100VNA-W

    Outdoor Unit : FDC100VNA-W

  • FDC100VNA-W
Indoor unit FDT100VH
Outdoor unit FDC100VNA-W
Power source 1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 2.73 / 2.54
EER/COP Cooling/Heating 3.66 / 4.41
Inrush current A 5
Max. running current A 24
Sound power
level*1
Indoor Cooling/Heating dB(A) 62 / 62
Outdoor Cooling/Heating 69 / 70
Sound pressure
level*1
Indoor Cooling (Hi/Me/Lo/Ulo) 47 / 39 / 36 / 30
Heating (Hi/Me/Lo/Ulo) 47 / 39 / 36 / 29
Outdoor Cooling/Heating 54 / 55
Air flow Indoor Cooling (Hi/Me/Lo/Ulo) m3/min 37 / 26 / 23 / 17
Heating (Hi/Me/Lo/Ulo) 37 / 26 / 23 / 17
Outdoor Cooling/Heating 75 / 73
Exterior Dimensions Indoor Height x Width x Depth mm Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
Outdoor 845 x 970 x 370
Net weight Indoor / Outdoor kg 30(Unit:25 Standard Panel:5) / 77
Refrigerant Type/GWP R32/675
Refrigerant Charge kg/TCO2Eq 3.3/2.228
Refrigerant piping size Liquid/Gas ø mm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences Outdoor is higher/lower m Max.50 / Max.15
Outdoor operating
temperature range
Cooling*2 °C -15~50
Heating -20~20
Panel White: T-PSA-5BW-E, T-PSAE-5BW-E / Black: T-PSA-5BB-E, T-PSAE-5BB-E
Air filter quantity Pocket plastic net x 1(Washable)
Remote control (option) White: RCN-T-5BW-E2 / Black: RCN-T-5BB-E2
Energy Class (Cooling/Heating) A++/A++
SEER 7.13
SCOP (Average climate) 4.60
Pdesign (cooling/heating(@-10°C)) kW 10.0/8.5
Annual Electricity Consumption (cooling/heating) kWh/a 491/2590
Designated Heating Season Average
The data is measured under the following conditions (ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
  3. : The values are for one indoor unit operation. (Multi system only)