FDF140VSXPVD1

14.0 ( 5.0 ~ 16.0 ) Floor Standing Multi Split PAC

FDF140VSXPVD1

Floor Standing : 14.0 ( 5.0 ~ 16.0 )

Indoor Unit - FDF71VD1 x 2 / Outdoor Unit - FDC140VSX
Nominal cooling capacity of 14.0kW

R410A
  • FDF71VD1 x 2
  • FDF71VD1 x 2

    Indoor Unit : FDF71VD1 x 2

    FDC140VSX

    Outdoor Unit : FDC140VSX

  • FDC140VSX
Indoor unit FDF71VD1 x 2
Outdoor unit FDC140VSX
Power source 3 Phase 380-415V, 50Hz / 380V 60Hz
Nominal cooling capacity (Min-Max) kW 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min-Max) kW 16.0 ( 4.0 ~ 20.0 )
Power Consumption Cooling/Heating kW 4.83/ 4.97
EER/COP Cooling/Heating kW 2.90 / 3.22
Inrush current A 5
Max. current A 15
Sound power level*1 Indoor*3 Cooling/Heating dB(A) 61 / 61
Outdoor Cooling/Heating 72 / 72
Sound pressure
level*1
Indoor*3 Cooling (P-Hi/Hi/Me/Lo) 42 / 39 / 35 / 33
Heating (P-Hi/Hi/Me/Lo) 42 / 39 / 35 / 33
Outdoor Cooling/Heating 49 / 52
Air flow Indoor*3 Cooling (P-Hi/Hi/Me/Lo) m3/min 18 / 16 / 14 / 12
Heating (P-Hi/Hi/Me/Lo) 18 / 16 / 14 / 12
Outdoor Cooling/Heating 100 / 100
Exterior
dimensions
Indoor HeightxWidthxDepth mm 1,850 x 600 x 320
Outdoor mm 1,300 x 970 x 370
Net weight Indoor/Outdoor kg 49 / 105
Refrigerant Type GWP R410A/2088
Ref.piping size Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences Outdoor is higher/lower m Max.30 / Max.15
Outdoor operating temperature range Cooling*2 °C -15~43
Heating °C -20~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control (option) wired:RC-E5 (installed) wireless:RCN-KIT4-E2 (option)
The data is measured under the following conditions (ISO-T1, -H1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions
  2. : If a cooling operation is conducted when the outdoor air temperature is —5°C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind, if wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down