12.5 ( 3.5 ~ 14.0 ) Floor Standing Single Split PAC

FDF125VSXWVH

Floor Standing : 12.5 ( 3.5 ~ 14.0 )

Indoor Unit - FDF125VH / Outdoor Unit - FDC125VSX-W
Nominal cooling capacity of 12.5kW

R32
  • FDF125VH
  • FDF125VH

    Indoor Unit : FDF125VH

    FDC125VSX-W

    Outdoor Unit : FDC125VSX-W

  • FDC125VSX-W
Indoor unitFDF125VH
Outdoor unitFDC125VSX-W
Power source3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min~Max)kW12.5 ( 3.5 ~ 14.0 )
Nominal heating capacity (Min~Max)kW14.0 ( 2.7 ~ 18.0 )
Power consumptionCooling/HeatingkW3.74 / 3.88
EER/COPCooling/Heating3.34 / 3.61
Inrush currentA5
Max. running currentA14
Sound power
level*1
IndoorCooling/HeatingdB(A)67 / 67
OutdoorCooling/Heating68 / 70
Sound pressure
level*1
IndoorCooling (Hi/Me/Lo/Ulo)55 / 51 / 49 / 44
Heating (Hi/Me/Lo/Ulo)55 / 51 / 49 / 44
OutdoorCooling/Heating53 / 54
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min29 / 26 / 23 / 19
Heating (Hi/Me/Lo/Ulo)29 / 26 / 23 / 19
OutdoorCooling/Heating100 / 100
Exterior DimensionsIndoorHeight x Width x Depthmm1,850 × 600 × 329
Outdoor1300 × 970 × 370
Net weightIndoor / Outdoorkg49 / 99
RefrigerantType/GWPR32
Refrigerant piping sizeLiquid/Gasø inch9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) lengthmMax.100
Vertical height differencesOutdoor is higher/lowermMax.50 / Max.15
Outdoor operating
temperature range
Cooling*2°C-15~50
Heating-20~20
Air filter quantityPlastic net x 1(washable)
Remote control (option)wired : RC-EX3A, RC-E5, RCH-E3 wireless : RCN-KIT4-E2
The data is measured under the following conditions (R32 : ISO-T1, -H1 / R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.