FDF125VNAWVH1

12.5 ( 5.0 ~ 14.0 ) Floor Standing Single Split PAC

FDF125VNAWVH1

Floor Standing : 12.5 ( 5.0 ~ 14.0 )

Indoor Unit - FDF125VH1 / Outdoor Unit - FDC125VNA-W
Nominal cooling capacity of 12.5kW

R32
  • FDF125VH1
  • FDF125VH1

    Indoor Unit : FDF125VH1

    FDC125VNA-W

    Outdoor Unit : FDC125VNA-W

  • FDC125VNA-W
Indoor unitFDF125VH1
Outdoor unitFDC125VNA-W
Power source1 Phase 220-240V, 50Hz / 220V, 60Hz
Nominal cooling capacity (Min~Max)kW12.5 ( 5.0 ~ 14.0 )
Nominal heating capacity (Min~Max)kW14.0 ( 4.0 ~ 16.0 )
Power consumptionCooling/HeatingkW4.65 / 4.10
EER/COPCooling/Heating2.69 / 3.42
Inrush currentA5
Max. running currentA24
Sound power
level*1
IndoorCooling/HeatingdB(A)67 / 67
OutdoorCooling/Heating71 / 71
Sound pressure
level*1
IndoorCooling (Hi/Me/Lo/Ulo)55 / 51 / 49 / 44
Heating (Hi/Me/Lo/Ulo)55 / 51 / 49 / 44
OutdoorCooling/Heating54 / 56
Air flowIndoorCooling (Hi/Me/Lo/Ulo)m3/min29 / 26 / 23 / 19
Heating (Hi/Me/Lo/Ulo)29 / 26 / 23 / 19
OutdoorCooling/Heating75 / 73
Exterior DimensionsIndoorHeight x Width x Depthmm1,850 × 600 × 329
Outdoor845 × 970 × 370
Net weightIndoor / Outdoorkg49 / 77
RefrigerantType/GWPR32/675
Refrigerant piping sizeLiquid/Gasmm (⌀ inch)9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) lengthmMax.50
Vertical height differencesOutdoor is higher/lowermMax.50 / Max.15
Outdoor operating
temperature range
Cooling*2°C-15~50
Heating-20~20
Air filter quantityPlastic net x 1(Washable)
Remote control (option)wired : RC-EX3A, RC-E5, RCH-E3 wireless : RCN-KIT4-E2
The data is measured under the following conditions (R32 : ISO-T1, -H1 / R410A : ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
  1. : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
  2. : If a cooling operation is conducted when the outdoor air temperature is –5 ̊C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.