Hydrolution Specifications

All-in-one combination

Indoor ModelHMK60HMK100HMK100
Outdoor ModelFDCW60VNX-AFDCW71VNX-AFDCW100VNX-A
Power source3 phase 400V  50Hz3 phase 400V  50Hz3 phase 400V  50Hz
Heating Nominal capacitycondition 1kW2.28 (0.50 – 8.00)8.0 (3.0 – 8.0)9.0 (3.5 – 11.0)
condition 2kW2.67 (0.50 -7.40)8.3 (2.0 – 8.3)9.2 (3.5 – 10.0)
COPcondition 13.623.333.44
condition 25.324.094.28
Cooling Nominal capacitycondition 1kW4.86 (0.80 -6.00)7.1 (2.0 – 7.1)8.0 (3.0 – 9.0)
condition 2kW7.03 (1.20 -7.80)10.7 (2.7 – 10.7)11.0 (3.3 – 12.0)
EERcondition 12.642.682.81
condition 23.523.353.62
Seasonal Space Heating *1
Energy Efficiency Class (W55/W35)
A++/A++A+/A+A++/A++
Water Heating Energy Efficiency Class *1AAA
Seasonal Space Heating
Energy Efficiency (W55/W35) *1
%188/138149/119165/126
Water Heating Energy Efficiency *1%919998
Seasonal Space Heating Energy *1 *2
Efficiency Class of package (W55/W35)
A+++/A++A++/A+A++/A++
Seasonal Space Heating Energy *1 *2
Efficiency of package (W55/W35)
192/142153/123169/130
Operation range (Ambient temperature)heating-20° – 43°
cooling15° – 43°
Operation range (Water temperature)heating25- 58 (65, with immersion heater)
cooling7-25
Max refrigerant pipe lengthm30
Max height difference between IU and OUm7
Indoor UnitHeight x Width x Depthmm1715(+ 40 max) x 600 x 6101715(+ 40 max) x 600 x 6101715(+ 40 max) x 600 x 610
Weight (without water in the system)kg165165165
Tank SurfaceEnamel Coated
Tank Volume totalliter180180180
Volume of coilliter4.84.84.8
Volume expansion vesselliter101010
Dimensions, climate system pipemm222222
Dimensions, hot water pipemm222222
Water pipe connectionsCompression fittings
Immersion HeaterKW9 (3 Step)

 

*1 European Average climate conditions
*2 In case of a room temperature sensor connected
*3 Sound pressure level is 1m away in front of outdoor unit at the height of 1m