Hydrolution Specifications

All-in-one combination

Indoor Model HMK60 HMK100 HMK100
Outdoor Model FDCW60VNX-A FDCW71VNX-A FDCW100VNX-A
Power source 3 phase 400V  50Hz 3 phase 400V  50Hz 3 phase 400V  50Hz
Heating Nominal capacity condition 1 kW 2.28 (0.50 – 8.00) 8.0 (3.0 – 8.0) 9.0 (3.5 – 11.0)
condition 2 kW 2.67 (0.50 -7.40) 8.3 (2.0 – 8.3) 9.2 (3.5 – 10.0)
COP condition 1 3.62 3.33 3.44
condition 2 5.32 4.09 4.28
Cooling Nominal capacity condition 1 kW 4.86 (0.80 -6.00) 7.1 (2.0 – 7.1) 8.0 (3.0 – 9.0)
condition 2 kW 7.03 (1.20 -7.80) 10.7 (2.7 – 10.7) 11.0 (3.3 – 12.0)
EER condition 1 2.64 2.68 2.81
condition 2 3.52 3.35 3.62
Seasonal Space Heating *1
Energy Efficiency Class (W55/W35)
A++/A++ A+/A+ A++/A++
Water Heating Energy Efficiency Class *1 A A A
Seasonal Space Heating
Energy Efficiency (W55/W35) *1
% 188/138 149/119 165/126
Water Heating Energy Efficiency *1 % 91 99 98
Seasonal Space Heating Energy *1 *2
Efficiency Class of package (W55/W35)
A+++/A++ A++/A+ A++/A++
Seasonal Space Heating Energy *1 *2
Efficiency of package (W55/W35)
192/142 153/123 169/130
Operation range (Ambient temperature) heating -20° – 43°
cooling 15° – 43°
Operation range (Water temperature) heating 25- 58 (65, with immersion heater)
cooling 7-25
Max refrigerant pipe length m 30
Max height difference between IU and OU m 7
Indoor Unit Height x Width x Depth mm 1715(+ 40 max) x 600 x 610 1715(+ 40 max) x 600 x 610 1715(+ 40 max) x 600 x 610
Weight (without water in the system) kg 165 165 165
Tank Surface Enamel Coated
Tank Volume total liter 180 180 180
Volume of coil liter 4.8 4.8 4.8
Volume expansion vessel liter 10 10 10
Dimensions, climate system pipe mm 22 22 22
Dimensions, hot water pipe mm 22 22 22
Water pipe connections Compression fittings
Immersion Heater KW 9 (3 Step)

 

*1 European Average climate conditions
*2 In case of a room temperature sensor connected
*3 Sound pressure level is 1m away in front of outdoor unit at the height of 1m