| Indoor Model | HMK60 | HMK100 | HMK100 | ||
| Outdoor Model | FDCW60VNX-A | FDCW71VNX-A | FDCW100VNX-A | ||
| Power source | 3 phase 400V 50Hz | 3 phase 400V 50Hz | 3 phase 400V 50Hz | ||
| Heating Nominal capacity | condition 1 | kW | 2.28 (0.50 – 8.00) | 8.0 (3.0 – 8.0) | 9.0 (3.5 – 11.0) |
| condition 2 | kW | 2.67 (0.50 -7.40) | 8.3 (2.0 – 8.3) | 9.2 (3.5 – 10.0) | |
| COP | condition 1 | 3.62 | 3.33 | 3.44 | |
| condition 2 | 5.32 | 4.09 | 4.28 | ||
| Cooling Nominal capacity | condition 1 | kW | 4.86 (0.80 -6.00) | 7.1 (2.0 – 7.1) | 8.0 (3.0 – 9.0) |
| condition 2 | kW | 7.03 (1.20 -7.80) | 10.7 (2.7 – 10.7) | 11.0 (3.3 – 12.0) | |
| EER | condition 1 | 2.64 | 2.68 | 2.81 | |
| condition 2 | 3.52 | 3.35 | 3.62 | ||
| Seasonal Space Heating *1 Energy Efficiency Class (W55/W35) | A++/A++ | A+/A+ | A++/A++ | ||
| Water Heating Energy Efficiency Class *1 | A | A | A | ||
| Seasonal Space Heating Energy Efficiency (W55/W35) *1 | % | 188/138 | 149/119 | 165/126 | |
| Water Heating Energy Efficiency *1 | % | 91 | 99 | 98 | |
| Seasonal Space Heating Energy *1 *2 Efficiency Class of package (W55/W35) | A+++/A++ | A++/A+ | A++/A++ | ||
| Seasonal Space Heating Energy *1 *2 Efficiency of package (W55/W35) | 192/142 | 153/123 | 169/130 | ||
| Operation range (Ambient temperature) | heating | -20° – 43° | |||
| cooling | 15° – 43° | ||||
| Operation range (Water temperature) | heating | 25- 58 (65, with immersion heater) | |||
| cooling | 7-25 | ||||
| Max refrigerant pipe length | m | 30 | |||
| Max height difference between IU and OU | m | 7 | |||
| Indoor Unit | Height x Width x Depth | mm | 1715(+ 40 max) x 600 x 610 | 1715(+ 40 max) x 600 x 610 | 1715(+ 40 max) x 600 x 610 |
| Weight (without water in the system) | kg | 165 | 165 | 165 | |
| Tank Surface | Enamel Coated | ||||
| Tank Volume total | liter | 180 | 180 | 180 | |
| Volume of coil | liter | 4.8 | 4.8 | 4.8 | |
| Volume expansion vessel | liter | 10 | 10 | 10 | |
| Dimensions, climate system pipe | mm | 22 | 22 | 22 | |
| Dimensions, hot water pipe | mm | 22 | 22 | 22 | |
| Water pipe connections | Compression fittings | ||||
| Immersion Heater | KW | 9 (3 Step) | |||
*1 European Average climate conditions
*2 In case of a room temperature sensor connected
*3 Sound pressure level is 1m away in front of outdoor unit at the height of 1m